← Selection Guides

Boilers

Engineering reference for commercial hydronic boiler specifications. Intended to help engineers consider all relevant factors � system design conditions, code compliance, venting, efficiency targets, and plant layout � before submitting for equipment selection.

Condensing vs. Non-Condensing

FactorCondensingNon-Condensing
AFUE / Thermal EfficiencyUp to 95�98%Up to 80�84%
Typical Capacity Range400 MBH � 3,000 MBH400 MBH � 6,000 MBH
Return Water Temp RequirementBelow 130�F for condensing operationNo minimum; operates at any return temp
Flue Gas Temp100�140�F300�450�F
Venting MaterialPVC, CPVC, Polypropylene, or SSType B, SS chimney liner, or AL29-4C
Condensate Drain RequiredYes � acidic condensate pH 3�4; must pipe to neutralization kit or approved drainNo
Heat Exchanger MaterialStainless steel or aluminum (corrosion-resistant)Cast iron, steel, or copper
First CostHigherLower
Operating CostLowerHigher
Best ApplicationLow-temp systems: radiant, fan coils, combination plants, ASHRAE 90.1 complianceHigh-temp systems: steam, non-condensing replacements, budget-constrained projects

When to use each

Per ASHRAE 90.1-2019 �6.5.4.8, gas boilers from 1,000,000 to 10,000,000 BTU/hr must achieve a minimum 90% thermal efficiency � effectively requiring condensing boilers on all new construction in this capacity range. Exceptions include:

  • On-site or recovered energy provides =25% of annual space heating
  • Boilers are installed in individual dwelling units
  • Perimeter convective heating or radiant ceiling panels serve =50% of the design heating load
  • Individual gas boilers have less than 300,000 BTU/hr input capacity

ASHRAE 90.1-2019 Efficiency Requirements

  • Boilers =2.5 million BTU/hr: minimum thermal efficiency (Et) of 75% for gas, 78% for oil
  • Boilers >2.5 million BTU/hr: minimum combustion efficiency (Ec) of 80% for gas, 83% for oil
  • Confirm which edition of ASHRAE 90.1 is adopted by the local Authority Having Jurisdiction (AHJ)

Selection Checklist

Load Sizing

  • Heating load calculation complete � block load, not sum of peaks unless diversity is accounted for
  • Safety factor applied (typically 10�15%; avoid oversizing beyond this)
  • Multiple boiler arrangement evaluated vs. single large boiler
  • DHW load separated or combined plant considered
  • Growth factor considered (typically 1% per year)

System Temperatures

  • Design supply water temperature confirmed
  • Design return water temperature confirmed
  • Design delta-T established (typically 20�40�F for hot water)
  • Return water temperature compatible with boiler type � condensing requires =130�F for peak efficiency
  • Outdoor reset schedule defined if applicable

Efficiency & Code

  • ASHRAE 90.1 edition confirmed with AHJ
  • Minimum efficiency requirement met for boiler capacity range
  • Exception applicability reviewed if using non-condensing above 1 MMBH
  • AFUE or thermal efficiency (Et) documented on equipment schedule

Turndown & Modulation

  • Turndown ratio specified � standard 4:1; high-performance 5:1, 10:1, or 15:1
  • Staging sequence defined for multiple boilers
  • Minimum fire rate compatible with minimum system load (prevents short-cycling)
  • Buffer tank evaluated if minimum fire rate exceeds minimum system load

Combustion & Venting

  • Fuel type confirmed: natural gas, LP, or dual fuel
  • Gas supply pressure confirmed with utility
  • Venting material specified per boiler type
  • Vent run length and termination clearances verified
  • Combustion air source identified: sealed combustion, mechanical room ventilation, or outdoor air
  • Condensate drain routed for condensing units � include neutralization kit
  • Local emissions and NOx requirements checked

Physical & Mechanical

  • Boiler footprint fits mechanical room layout
  • Floor loading verified (especially for roof-mounted or upper-floor installations)
  • Rigging path confirmed for boiler delivery
  • Service clearances provided per manufacturer requirements
  • Piping connections sized and oriented correctly
  • Electrical supply confirmed: voltage, phase, amperage
  • Boiler water volume documented for buffer tank and expansion tank calculations

Controls Integration

  • BMS/BAS integration protocol confirmed: BACnet, Modbus, or LON
  • Lead-lag sequence defined for multiple boilers
  • Outdoor air reset control specified
  • High-limit and low-limit safeties defined
  • NFPA 85 compliance addressed for boilers =12.5 MMBH input

Combination Plant Considerations

When the boiler plant serves both space heating and DHW:

  • Evaluate a "swing boiler" concept � certain boilers assigned to heating, others to DHW, with the ability to reassign based on load
  • Per ASHRAE, peak space heating and peak DHW loads rarely occur simultaneously � this can reduce total installed boiler capacity
  • A combined plant improves condensing efficiency because DHW return temps are typically lower (boosting condensation rate)
  • Ensure proper hydraulic separation between heating and DHW circuits
  • Confirm the boiler is rated for potable water contact if directly heating DHW, or specify an indirect heat exchanger

Key Design References

  • ASHRAE 90.1-2019 �6.5.4.8 Boiler efficiency requirements
  • ASHRAE Handbook: HVAC Systems and Equipment, Chapter 32 Boilers
  • ASME Boiler & Pressure Vessel Code, Section IV Heating boilers
  • NFPA 85 Boiler and Combustion Systems Hazards Code
  • Local mechanical code IMC or equivalent adopted edition