Selection Guide
Coil Piping Packages
Engineering reference for coil piping packages (CPPs / runout kits) at terminal units � VAV reheat coils, fan coils, AHU coils, induction units, and chilled beams. Covers valve type and authority, actuator signal, isolation method, balancing strategy, and pressure class.
What a Coil Piping Package Contains
A complete CPP at a hydronic terminal unit typically includes:
| Component | Purpose |
|---|---|
| Isolation Valves (2) | Allow coil to be removed without draining the system; ball valve standard, butterfly above 2-1/2" |
| Strainer | Protects control valve from debris; typically Y-type with blowdown valve |
| Control Valve | Modulates flow to coil; 2-way (variable flow) or 3-way (constant flow, legacy) |
| Actuator | Drives the control valve; floating, 2-position, or modulating (0�10V / 4�20mA) |
| Balancing Valve | Sets design flow on constant-flow systems; not required with PICVs |
| Union or Flange | Allows coil disconnection without cutting pipe |
| P/T Test Ports | Field verification of flow and temperature at supply and return |
| Air Vent / Drain | Manual or automatic; required at coil high point |
2-Way vs. 3-Way vs. PICV
| Factor | 2-Way Modulating | 3-Way (Mixing or Diverting) | PICV |
|---|---|---|---|
| System Flow | Variable | Constant | Variable |
| Pump Energy Savings | Yes (with VFD pumps) | None | Yes |
| ASHRAE 90.1 Compliance | Required above 10 HP pump systems | Allowed only in specific exceptions | Required / preferred |
| Valve Authority Design Effort | High � must match Cv to coil ?P at design | None � bypass legs balance the loop | Built-in � integral pressure regulator handles authority |
| Balancing Required | Manual balance required | Manual balance required | None � flow setpoint dialed in |
| First Cost | Lower | Lower | Higher |
| Commissioning Time | Significant | Significant | Minimal |
| Best Application | Smaller systems where commissioning is well-controlled | Legacy retrofits, snow melt, specific equipment requirements | Modern variable-flow systems, large building distribution, fast commissioning |
Actuator Selection
| Signal Type | Use Case | Notes |
|---|---|---|
| Floating (3-Wire) On/Off/Stop | Simple modulation from a thermostat | Lower cost; slower response; no positive position feedback unless specified |
| 2-Position (On/Off) | Snow melt, simple zone control | Spring-return preferred for fail-safe close |
| 0�10 VDC Modulating | BMS-controlled VAV reheat, fan coils | Most common in commercial spec |
| 4�20 mA Modulating | Industrial / longer cable runs / noisy environments | More immune to electrical noise |
| Spring-Return (Fail-Safe) | Critical applications � fail open or fail closed | Required where loss of power could damage coil (e.g., chilled water coils that could freeze) |
Verify torque requirements against the valve manufacturer's published close-off pressure. Undersized actuators are a leading cause of leaking control valves in service.
Selection Checklist
Flow & Pressure
- Coil design GPM and ?T documented
- Coil pressure drop at design flow confirmed from manufacturer data
- System differential pressure at the coil documented: min and max, accounting for variable-flow pressure swings
- Control valve type selected: 2-way modulating, 2-way 2-position, 3-way, or PICV
- Valve Cv sized for required ?P � confirm authority � = 0.5 if not using PICV
- Maximum close-off pressure verified against actuator torque rating
Components
- Isolation valve type by line size: ball for =2", butterfly for =2-1/2"
- Strainer included with blowdown valve and stainless steel screen (20 mesh standard for hot water; finer for chilled water with low-temp glycol)
- Balancing valve specified if not using PICV
- P/T test ports included on supply and return
- Air vent and drain provided
- Unions or flanges on both sides of the control valve to permit removal
Actuator
- Actuator signal type matches BMS specification (0�10V most common)
- Spring-return vs. non-spring-return decision documented
- Actuator pre-wired to valve from manufacturer specified where possible
- Actuator location accessible after coil installation
- 24V transformer load checked: actuator VA + cable losses within transformer rating
Pressure & Materials
- Pressure class matches system: 150# or 300# typical for commercial
- Bronze or stainless trim for chilled water with high oxygen exposure
- Body material: forged brass (small sizes), bronze, or ductile iron (larger sizes)
- O-rings and seats compatible with system fluid and temperature
- Lead-free brass specified for any potable water contact
Installation
- Connection type matches piping: sweat, threaded, press, grooved, or flanged
- Coil kit assembled and pressure tested at the factory (preferred) or pre-cut and bagged for field assembly
- Shipping configuration documented: full assembly, pre-cut with fittings, or components only
- Insulation requirements specified � chilled water requires vapor-tight insulation
- Heat trace requirements identified for outdoor or unconditioned spaces
Commissioning
- Method statement for setting design flow defined: PICV setpoint, balancing valve handle position, or DP measurement
- Test report deliverable required (yes/no) documented
- BMS integration verified: signal commands match valve position at multiple set points
- Coil capacity verified at design flow and design supply temperature
Counting Coil Kits from a VAV Schedule
For takeoff purposes, the count of coil kits equals the count of hydronic-served terminal units. The VAV or fan coil schedule typically includes:
- Tag (e.g., VAV-1-01)
- Coil type: HW reheat, CHW cooling, or both
- Design GPM
- Design EWT/LWT (entering and leaving water temperature)
- Coil pressure drop at design flow
- Connection size
Group coil kits by line size and valve type for the most efficient quote. For mixed-size projects, separate the takeoff into bins � for example: 1/2" HW reheat, 3/4" HW reheat, 1" CHW coils.
Common Selection Mistakes
- Oversizing control valves to match line size instead of sizing to Cv � destroys valve authority and causes hunting
- Specifying PICVs without confirming actuator-to-valve compatibility from the same manufacturer
- Mixing 2-way valves on terminals with constant-flow primary pumps � starves the boiler or chiller of minimum flow
- Forgetting the air vent at the coil high point � air binds the coil and reduces capacity with no visible indication
- Undersizing actuator torque relative to close-off pressure � leads to leaking valves and failed commissioning
- Using 3-way valves on systems that require ASHRAE 90.1 variable-flow compliance without reviewing applicable exceptions