← Selection Guides

Coil Piping Packages

Engineering reference for coil piping packages (CPPs / runout kits) at terminal units � VAV reheat coils, fan coils, AHU coils, induction units, and chilled beams. Covers valve type and authority, actuator signal, isolation method, balancing strategy, and pressure class.

What a Coil Piping Package Contains

A complete CPP at a hydronic terminal unit typically includes:

ComponentPurpose
Isolation Valves (2)Allow coil to be removed without draining the system; ball valve standard, butterfly above 2-1/2"
StrainerProtects control valve from debris; typically Y-type with blowdown valve
Control ValveModulates flow to coil; 2-way (variable flow) or 3-way (constant flow, legacy)
ActuatorDrives the control valve; floating, 2-position, or modulating (0�10V / 4�20mA)
Balancing ValveSets design flow on constant-flow systems; not required with PICVs
Union or FlangeAllows coil disconnection without cutting pipe
P/T Test PortsField verification of flow and temperature at supply and return
Air Vent / DrainManual or automatic; required at coil high point

2-Way vs. 3-Way vs. PICV

Factor2-Way Modulating3-Way (Mixing or Diverting)PICV
System FlowVariableConstantVariable
Pump Energy SavingsYes (with VFD pumps)NoneYes
ASHRAE 90.1 ComplianceRequired above 10 HP pump systemsAllowed only in specific exceptionsRequired / preferred
Valve Authority Design EffortHigh � must match Cv to coil ?P at designNone � bypass legs balance the loopBuilt-in � integral pressure regulator handles authority
Balancing RequiredManual balance requiredManual balance requiredNone � flow setpoint dialed in
First CostLowerLowerHigher
Commissioning TimeSignificantSignificantMinimal
Best ApplicationSmaller systems where commissioning is well-controlledLegacy retrofits, snow melt, specific equipment requirementsModern variable-flow systems, large building distribution, fast commissioning

Sizing Control Valves for Authority

For traditional 2-way modulating valves, valve authority (�) should be 0.5 or higher for stable modulating control:

� = ?Pvalve � (?Pvalve + ?Pcoil + ?Pbalance + ?Pstrainer)

This means the fully-open valve pressure drop should be at least equal to the rest of the coil-circuit pressure drop. In practice:

  • Target valve ?P at design flow: 1.5�5 ft (3�12 ft for systems with high distribution head)
  • Avoid oversized valves � a Cv larger than needed produces low authority and unstable control
  • For VAV reheat coils, valve ?P at design typically ranges 2�5 ft
  • PICVs eliminate the authority sizing exercise because the integral differential pressure regulator maintains the same ?P across the control element regardless of system pressure changes

Actuator Selection

Signal TypeUse CaseNotes
Floating (3-Wire) On/Off/StopSimple modulation from a thermostatLower cost; slower response; no positive position feedback unless specified
2-Position (On/Off)Snow melt, simple zone controlSpring-return preferred for fail-safe close
0�10 VDC ModulatingBMS-controlled VAV reheat, fan coilsMost common in commercial spec
4�20 mA ModulatingIndustrial / longer cable runs / noisy environmentsMore immune to electrical noise
Spring-Return (Fail-Safe)Critical applications � fail open or fail closedRequired where loss of power could damage coil (e.g., chilled water coils that could freeze)

Verify torque requirements against the valve manufacturer's published close-off pressure. Undersized actuators are a leading cause of leaking control valves in service.

Selection Checklist

Flow & Pressure

  • Coil design GPM and ?T documented
  • Coil pressure drop at design flow confirmed from manufacturer data
  • System differential pressure at the coil documented: min and max, accounting for variable-flow pressure swings
  • Control valve type selected: 2-way modulating, 2-way 2-position, 3-way, or PICV
  • Valve Cv sized for required ?P � confirm authority � = 0.5 if not using PICV
  • Maximum close-off pressure verified against actuator torque rating

Components

  • Isolation valve type by line size: ball for =2", butterfly for =2-1/2"
  • Strainer included with blowdown valve and stainless steel screen (20 mesh standard for hot water; finer for chilled water with low-temp glycol)
  • Balancing valve specified if not using PICV
  • P/T test ports included on supply and return
  • Air vent and drain provided
  • Unions or flanges on both sides of the control valve to permit removal

Actuator

  • Actuator signal type matches BMS specification (0�10V most common)
  • Spring-return vs. non-spring-return decision documented
  • Actuator pre-wired to valve from manufacturer specified where possible
  • Actuator location accessible after coil installation
  • 24V transformer load checked: actuator VA + cable losses within transformer rating

Pressure & Materials

  • Pressure class matches system: 150# or 300# typical for commercial
  • Bronze or stainless trim for chilled water with high oxygen exposure
  • Body material: forged brass (small sizes), bronze, or ductile iron (larger sizes)
  • O-rings and seats compatible with system fluid and temperature
  • Lead-free brass specified for any potable water contact

Installation

  • Connection type matches piping: sweat, threaded, press, grooved, or flanged
  • Coil kit assembled and pressure tested at the factory (preferred) or pre-cut and bagged for field assembly
  • Shipping configuration documented: full assembly, pre-cut with fittings, or components only
  • Insulation requirements specified � chilled water requires vapor-tight insulation
  • Heat trace requirements identified for outdoor or unconditioned spaces

Commissioning

  • Method statement for setting design flow defined: PICV setpoint, balancing valve handle position, or DP measurement
  • Test report deliverable required (yes/no) documented
  • BMS integration verified: signal commands match valve position at multiple set points
  • Coil capacity verified at design flow and design supply temperature

Counting Coil Kits from a VAV Schedule

For takeoff purposes, the count of coil kits equals the count of hydronic-served terminal units. The VAV or fan coil schedule typically includes:

  • Tag (e.g., VAV-1-01)
  • Coil type: HW reheat, CHW cooling, or both
  • Design GPM
  • Design EWT/LWT (entering and leaving water temperature)
  • Coil pressure drop at design flow
  • Connection size

Group coil kits by line size and valve type for the most efficient quote. For mixed-size projects, separate the takeoff into bins � for example: 1/2" HW reheat, 3/4" HW reheat, 1" CHW coils.

Common Selection Mistakes

  • Oversizing control valves to match line size instead of sizing to Cv � destroys valve authority and causes hunting
  • Specifying PICVs without confirming actuator-to-valve compatibility from the same manufacturer
  • Mixing 2-way valves on terminals with constant-flow primary pumps � starves the boiler or chiller of minimum flow
  • Forgetting the air vent at the coil high point � air binds the coil and reduces capacity with no visible indication
  • Undersizing actuator torque relative to close-off pressure � leads to leaking valves and failed commissioning
  • Using 3-way valves on systems that require ASHRAE 90.1 variable-flow compliance without reviewing applicable exceptions